What does Ontario's 2026 fire alarm rule require?
Short answer
From 1 January 2026 the Ontario Fire Code names the 2019 edition of CAN/ULC-S536 for inspecting and testing fire alarm systems, and the 2019 edition of CAN/ULC-S537 for verifying them. O. Reg. 87/25 made the change.
Edition: CAN/ULC-S536-2019Updated 2026-11-22Source: O. Reg. 87/25, on e-Laws
Which regulation made the change?
O. Reg. 87/25 amended the Ontario Fire Code (O. Reg. 213/07). It was made on 2 June 2025 and filed on 4 June 2025. Its fire alarm provisions came into force on 1 January 2026.
O. Reg. 303/25, made on 9 December 2025, corrected the titles of the two standards and restated the affected sentences. It also came into force on 1 January 2026.
Table 1.2.1.A of the Fire Code now lists CAN/ULC-S536-2019 for Sentences 6.3.2.2.(1) to (3) and Article 6.3.2.4, and CAN/ULC-S537-2019 for Sentence 9.9.4.12.(2).
What does the Fire Code itself say?
Subsection 6.3.2 of Division B sets the duties. In short:
- 6.3.2.2.(1): a fire alarm system is inspected and tested in conformance with CAN/ULC-S536.
- 6.3.2.2.(3): a description of the system is kept current, in the building, at an approved location.
- 6.3.2.2.(4): a record of each device, component and circuit shows whether it is in proper working order.
- 6.3.2.2.(5): where the system is monitored, the owner records whether the monitoring station received the test signals.
- 6.3.2.3: the central alarm and control facility is checked daily for indication of trouble.
- 6.3.2.4: voice communication that is integrated with the fire alarm system is tested in conformance with CAN/ULC-S536.
What changes in the report?
The Fire Code does not describe the report form. The standard does, and it is not reproduced here. Tap Report and EPI Fire Protection, through OECM, have published summaries of the change. They describe it this way:
| Before | From 2026 |
|---|---|
| Voltage check on batteries | Load test with recorded values |
| Free-form deficiency notes | A table that cites the clause |
| No record of who attended | Attendance log with times |
| Report handed over | Owner signs off after repairs |
See what the 2019 report requires for the full list.
Does an existing system have to be changed?
Sentence 1.2.1.1.(2) says an installation that met the requirements on 31 December 2025, and still meets them, is deemed to comply with the edition in the table. That sentence is about the installation. Inspection and testing done from 1 January 2026 follow the 2019 edition.
Article 1.2.1.3 lets the Chief Fire Official permit an earlier edition of a referenced document. Ask your fire department before relying on that.
Is it the 2019 or the 2024 edition?
The table in the Fire Code names CAN/ULC-S536-2019. Some supplier material, including the OECM update linked above, names a 2024 edition. The text of the regulation governs. Article 1.2.1.2 adds that a referenced document includes its amendments effective to 1 January 2026.
Sources
- O. Reg. 87/25, on e-Laws
- O. Reg. 303/25, on e-Laws
- Ontario Fire Code, O. Reg. 213/07, on e-Laws
- Tap Report: the difference between CAN/ULC-S536-04 and CAN/ULC-S536-19
- OECM and EPI Fire Protection: battery load testing requirements